TIMS
can accurately measure and store data from
the K thermocouple port (10channels), the
analog port (8 channels),
and the digital input port (4channels).
For remote monitoring of devices and systems,
data can be
transferred through various communication lines at low cost.
TIMS can measure temperatures from -200 to 1200ºC
with
a resolution of 0.1ºC. And it can log
a maximum of 23000 times
the amount of data in its internal memory. Logging pace can be
freely set from a minimum of 1 second to
a maximum of 3600 seconds.
A logging pace of 60 seconds will result in more than 6 months of data.
|
Input
| Item |
Specifications
and recommended operating conditions |
| Analog voltage |
0 to +5V, 5mV resolution, 8ch |
| Digital input |
contact point input, open collector input,
4ch |
| Digital output |
LED lighting or equal load, 4ch |
| Temperature measurement, K thermocouple |
0 to 100% RH (option) |
|
|
| Working temperature range |
-30 to 80ºC |
| Working humidity limit |
up to 90%RH (option) |
Interface
| Item |
Specifications |
| Standard |
RS232C, RS485 (for expansion up to a maximum
of 100 units) |
| Baud rate |
115200, 57600, 38400, 19200, 9600, 4800,
2400bps |
| Method |
pace synchronous transmission |
Function
| Item |
Specifications and
recommended operating conditions |
| Power supply |
|
| AC adapter |
Input voltage 100V |
| DC Input |
8V to 16V |
| Built-in NiMH battery |
4.8V 1200mAh |
| Size |
100mm(W) ×
35mm(H) ×126mm(D) |
| Weight |
550g, including battery |
*The TIMS system will be
released next year.
|